Rem. |
Parameter |
Description |
Minimum |
Maximum |
Default |
Unit |
| S__ | | | Functions about storage | | | | |
| | St_ | | Functions about storage temperature | | | | |
| | | _t0 | storage room temperature | -55.0 | 145.0 | 12.0 | °C |
| | | _db | dead band | 0.0 | 50.0 | 0.0 | K |
| | | dbd | differential | 0.0 | 50.0 | 0.2 | K |
| | | _tH | safety maximum room temperature | -55.0 | 45.0 | 21.0 | °C |
| | | _tL | safety minimum room temperature | -55.0 | 45.0 | 10.0 | °C |
| | | _td | safety temperature differential | 0.0 | 50.0 | 0.2 | K |
| | | SMM | storage room humidity | 0.0 | 100.0 | 90.0 | % |
| | | SMd | differential | 0.0 | 50.0 | 5.0 | % |
| | SA_ | | Functions about air renew during storage | | | | |
1 | | | SAH | enable air renew during storage - reset timers | oFF | _on | oFF | / |
| | | dA6 | immediate delay before first air renew | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | dA7 | on-time duration in the air renew cycle | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
2 | | | dA8 | period of air renew cycle | 0 | 194 4:20:15 | 12:00:00 | dd hh:mm:ss |
| | | SAh | enable forced air renew by keyboard short cut | oFF | _on | _on | / |
| | | dAF | forced air renew duration | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | SAo | start / stop forced air renew | oFF | _on | oFF | / |
| r__ | | | Functions about ripening | | | | |
| | rH_ | | Enable ripening functions and short cut | | | | |
3 | | | rrH | enable ripening functions - reset timers | oFF | _on | oFF | / |
| | | rrh | enable toggling between ripening and storage by keyboard short cut | oFF | _on | _on | / |
| | rt_ | | Functions about ripening temperature and humidity | | | | |
| | | _d0 | immediate delay before starting ripening | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | _t1 | ripening temperature nr. 1 | -55.0 | 45.0 | 16.5 | °C |
| | | _d1 | duration of temperature nr. 1 | 0 | 194 4:20:15 | 4 0:00:00 | dd hh:mm:ss |
| | | _t2 | ripening temperature nr. 2 | -55.0 | 45.0 | 15.5 | °C |
| | | _d2 | duration of temperature nr. 2 | 0 | 194 4:20:15 | 1 0:00:00 | dd hh:mm:ss |
| | | _t3 | ripening temperature nr. 3 | -55.0 | 45.0 | 14.5 | °C |
| | | _d3 | duration of temperature nr. 3 | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | _t4 | ripening temperature nr. 4 | -55.0 | 45.0 | 14.5 | °C |
| | | _d4 | duration of temperature nr. 4 | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
4 | | | _t5 | ripening temperature nr. 5 | -55.0 | 45.0 | 14.5 | °C |
| | | rMM | ripening humidity | 0.0 | 100.0 | 90.0 | % |
| | | rMd | ripening humidity differential | 0.0 | 50.0 | 5.0 | % |
| | rY_ | | Functions about ethylene | | | | |
5 | | | rYH | enable ethylene injection - reset timers | oFF | _on | oFF | / |
6 | | | YYb | use ethylene probe to control injections | oFF | _on | oFF | / |
| | | rYY | ripening ethylene concentration | 0.0 | 99.0 | 25.0 | 10*ppm |
| | | rYd | ripening ethylene concentration differential | 0.0 | 99.0 | 5.0 | 10*ppm |
7 | | | dY0 | immediate delay before starting ripening | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
8 | | | _tY | minimum temperature before injecting ethylene | -55.0 | 45.0 | 16.0 | °C |
| | | dY2 | first ethylene injection duration | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | _nY | number of following ethylene cycles of injection | 0 | 255 | 0 | / |
9 | | | dY3 | delay between first ethylene injections end and following cycles | 0 | 194 4:20:15 | 1 0:00:00 | dd hh:mm:ss |
| | | dY4 | on-time duration of following ethylene injection cycles | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
10 | | | dY5 | period of following ethylene injection cycles | 0 | 194 4:20:15 | 12:00:00 | dd hh:mm:ss |
| | | rYh | enable forced ethylene injection by keyboard short cut | oFF | _on | _on | / |
| | | dYF | forced ethylene injection duration | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | rYo | start / stop forced ethylene injection | oFF | _on | oFF | / |
11 | | | rYA | first ethylene injection performed but air renew not yet | oFF | _on | oFF | / |
| | rA_ | | Functions about air renew during ripening | | | | |
| | | rAH | enable air renew cycles during ripening - reset timers | oFF | _on | oFF | / |
| | | _nA | number of air renew cycles | 0 | 99 | 8 | / |
9 | | | dA3 | delay between first ethylene injection end and first air renew end | 0 | 194 4:20:15 | 1 0:00:00 | dd hh:mm:ss |
| | | dA4 | on-time duration in the air renew cycle | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
10 | | | dA5 | period of air renew cycle | 0 | 194 4:20:15 | 12:00:00 | dd hh:mm:ss |
| | | rAh | enable forced air renew by keyboard short cut | oFF | _on | _on | / |
| | | rAF | forced air renew duration | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | rAo | start / stop forced air renew | oFF | _on | oFF | / |
| n__ | | | Functions about fans | | | | |
| | nU_ | | Functions about depression fans | | | | |
| | | nUS | number of depression fans during storage | 0 | 3 | 2 | / |
| | | nUr | number of depression fans during ripening | 0 | 3 | 3 | / |
| | nE_ | | Functions about evaporator fans | | | | |
| | | nEH | force evaporator fans when refrigeration is off | oFF | _on | oFF | / |
| P__ | | | Functions about master preferences | | | | |
| | Pd_ | | Functions about network address | | | | |
| | | PdM | master address for global network communication | 0 | 254 | 1 | / |
| | | PdS | number of slaves connected to this master | 1 | 2 | 2 | / |
| | | Pd2 | number of auxiliary masters connected to this master | 0 | 2 | 2 | / |
| | Pg_ | | Functions about saving preferences | | | | |
| | | Pgg | save actual preferences as program 1 ... 99 | 1 | 99 | 1 | / |
| | Pj_ | | Functions about loading preferences | | | | |
| | | Pjh | enable preferences load by keyboard short-cut | oFF | _on | oFF | / |
| | | Pjj | load preferences as program 0 ... 99 (0 is factory setting) | 0 | 99 | 0 | / |
| | PO_ | | Output assignment | | | | |
| | | PO2 | assign out-2 relay to: 0=alarm / 1=humidifier | 0 | 1 | 1 | / |
| c__ | | | Functions about door and light | | | | |
| | cO_ | | Functions about door | | | | |
12 | | | cOh | enable door operation from keyboard | oFF | _on | _on | / |
13 | | | cOF | enable door flashing light in case of alarm | oFF | _on | _on | / |
14 | | | cOd | delay between pushing button and door opening or closure | 0 | 194 4:20:15 | 2 | dd hh:mm:ss |
| | | cOH | enable door automatic closure | oFF | _on | oFF | / |
| | | cCd | delay of door automatic closure | 0 | 194 4:20:15 | 30 | dd hh:mm:ss |
| | | cOU | enable depressure, refrigeration and other output when door is not closed | oFF | _on | oFF | / |
| | | cOY | enable door opening after first ethylene injection and before first air renew | oFF | _on | _on | / |
| | cI_ | | Functions about light | | | | |
15 | | | cIO | switch on the light during door operation | oFF | _on | _on | / |
| | | cIH | switch on the light when the door is open and off when closed | oFF | _on | _on | / |
16 | | | cIo | switch off the light automatically if it has been switched on from outside | oFF | _on | _on | / |
| | | cId | delay of light automatic switch off | 0 | 194 4:20:15 | 30 | dd hh:mm:ss |
| | cc_ | | Functions about curtain operation | | | | |
17 | | | cch | enable curtain operation from keyboard | oFF | _on | oFF | / |
18 | | | ccc | keyboard in curtain mode | oFF | _on | oFF | / |
15 | | | ccO | enable curtain operation when door is not open | oFF | _on | oFF | / |
15 | | | ccI | enable curtain operation when light is off | oFF | _on | oFF | / |
| v__ | | | Functions about electronic expansion valve | | | | |
| | vP_ | | Functions about electronic expansion valve preference | | | | |
19 | | | vPH | enable electronic expansion valve | oFF | _on | _on | / |
| | vt_ | | Functions about electronic expansion valve temperature | | | | |
20 | | | vtt | wanted overheating (similar to Danfoss thermostatic overheating spring regulation) | 0.0 | 99.0 | 8.0 | K |
| | | vtU | maximum pressure allowed in the suction line (similar to Danfoss MOP) | 0.0 | 30.0 | 10.0 | (gauge) bar |
| | vd_ | | Functions about electronic expansion valve timing | | | | |
21 | | | vd1 | on-off duty cycle duration | 0 | 194 4:20:15 | 8 | dd hh:mm:ss |
22 | | | vd2 | on duty cycle duration at refrigeration start (set to 0 for previous stop value) | 0 | 194 4:20:15 | 5 | dd hh:mm:ss |
23 | | | vdd | on duty cycle adaptation speed (low value for slow adaptation and small swinging) | 0 | 255 | 8 | / |
| b__ | | | Functions about probe calibration | | | | |
| | b1_ | | Probe nr. 1 | | | | |
| | | b1C | calibration offset | -9.0 | 9.0 | 0.0 | K |
| | | b1A | use probe to calculate product average temperature | oFF | _on | oFF | / |
| | | b1S | use probe for safety temperature | oFF | _on | _on | / |
| | | b1L | use probe for alarm temperature | oFF | _on | _on | / |
| | b2_ | | Probe nr. 2 | | | | |
| | | b2C | calibration offset | -9.0 | 9.0 | 0.0 | K |
| | | b2A | use probe to calculate product average temperature | oFF | _on | _on | / |
| | | b2S | use probe for safety temperature | oFF | _on | _on | / |
| | | b2L | use probe for alarm temperature | oFF | _on | _on | / |
| | b3_ | | Probe nr. 3 | | | | |
| | | b3C | calibration offset | -9.0 | 9.0 | 0.0 | K |
| | | b3A | use probe to calculate product average temperature | oFF | _on | oFF | / |
| | | b3S | use probe for safety temperature | oFF | _on | oFF | / |
| | | b3L | use probe for alarm temperature | oFF | _on | oFF | / |
| | b4_ | | Probe nr. 4 | | | | |
| | | b4C | calibration offset | -9.0 | 9.0 | 0.0 | K |
| | | b4A | use probe to calculate product average temperature | oFF | _on | _on | / |
| | | b4S | use probe for safety temperature | oFF | _on | _on | / |
| | | b4L | use probe for alarm temperature | oFF | _on | _on | / |
| | b5_ | | Probe nr. 5 | | | | |
| | | b5C | calibration offset | -9.0 | 9.0 | 0.0 | % |
| | | b5A | use probe to calculate room humidity | oFF | _on | _on | / |
| | b6_ | | Probe nr. 6 | | | | |
| | | b6C | calibration offset | -9.0 | 9.0 | 0.0 | 10*ppm |
| | | b6A | use probe to calculate room ethylene | oFF | _on | oFF | / |
| | b7_ | | Probe nr. 7 | | | | |
| | | b7C | calibration offset | -9.0 | 9.0 | 0.0 | bar |
| | | b7A | use probe to calculate suction pressure | oFF | _on | _on | / |
| L__ | | | Functions about alarm and stand-by | | | | |
| | Lt_ | | Temperature alarm | | | | |
24 | | | LtL | low temperature alarm set point | -55.0 | 145.0 | -2.0 | °C |
25 | | | LtH | high temperature alarm set point | -55.0 | 145.0 | 14.0 | °C |
| | | Ltd | alarm delay | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | Lo_ | | On / stand-by status | | | | |
26 | | | Loo | actual status: stand-by or on | oFF | _on | oFF | / |
| d__ | | | Functions about delays | | | | |
| | dF_ | | Delay from previous stop | | | | |
| | | dF6 | delay from request to activation of OUT-6: heating | 0 | 194 4:20:15 | 3:00 | dd hh:mm:ss |
| h__ | | | Functions about keyboard | | | | |
| | hL_ | | Keyboard lock | | | | |
27 | | | hLH | keyboard lock / unlock | oFF | _on | oFF | / |
| | | hLP | keyboard lock / unlock password | 0 | 99 | 22 | / |
| | | hLI | extend lock to light operation | oFF | _on | oFF | / |
| | | hLc | extend lock to curtain operation | oFF | _on | _on | / |
| | | hLO | extend lock to door operation | oFF | _on | _on | / |
| I__ | | | Functions about input-output and machine state (read only) | | | | |
| | IA_ | | Analog inputs | | | | |
| | | IA1 | analog input 1 (temperature) | -55.0 | 145.0 | -55.0 | °C |
| | | IA2 | analog input 2 (temperature) | -55.0 | 145.0 | -55.0 | °C |
| | | IA3 | analog input 3 (suction temperature) | -55.0 | 145.0 | -55.0 | °C |
| | | IA4 | analog input 4 (temperature) | -55.0 | 145.0 | -55.0 | °C |
| | | IA5 | analog input 5 (humidity) | 0.0 | 100.0 | 0.0 | % |
| | | IA6 | analog input 6 (ethylene) | 0.0 | 999.0 | 0.0 | 10*ppm |
| | | IA7 | analog input 7 (low pressure) | 0.0 | 999.0 | 0.0 | (gauge) bar |
| | | IA8 | analog input 8 | -55.0 | 145.0 | -55.0 | °C |
| | Id_ | | Digital input | | | | |
| | | Id1 | digital input 1 (ethylene hardware safety) | oFF | _on | oFF | / |
| | | Id2 | digital input 2 (evaporator hardware safety) | oFF | _on | oFF | / |
| | | Id3 | digital input 3 (heating hardware safety) | oFF | _on | oFF | / |
| | | Id4 | digital input 4 (unused) | oFF | _on | oFF | / |
| | | Id5 | digital input 5 (phase-1 software safety ) | oFF | _on | oFF | / |
| | OA_ | | Analog output | | | | |
| | | OA1 | analog output "FAN" | 0 | 255 | 0 | / |
| | | OA2 | analog output "I out" | 0 | 255 | 0 | / |
| | Od_ | | Digital output | | | | |
| | | Od1 | digital output 1 (refrigeration solenoid) | oFF | _on | oFF | / |
| | | Od2 | digital output 2 (steam producer) | oFF | _on | oFF | / |
| | | Od3 | digital output 3 (air renew) | oFF | _on | oFF | / |
| | | Od4 | digital output 4 (ethylene) | oFF | _on | oFF | / |
| | | Od5 | digital output 5 (evaporator) | oFF | _on | oFF | / |
| | | Od6 | digital output 6 (heating) | oFF | _on | oFF | / |
| | | Od7 | alarm - eventually connected to relay nr. 2 | oFF | _on | oFF | / |
| | OS_ | | Machine status | | | | |
| | | Ido | door fully open | oFF | _on | oFF | / |
| | | Idc | door fully closed | oFF | _on | oFF | / |
| | | Idh | door safety | oFF | _on | oFF | / |
| | | IdP | door is presumed to be closed, combining history of door closure and safety | oFF | _on | oFF | / |
| | | Ib7 | button B8 is pressed | oFF | _on | oFF | / |
| | | Ib8 | button B7 is pressed | oFF | _on | oFF | / |
| | | In1 | safety of depressure fan 1 | oFF | _on | oFF | / |
| | | In2 | safety of depressure fan 2 | oFF | _on | oFF | / |
| | | In3 | safety of depressure fan 3 | oFF | _on | oFF | / |
| | | OS0 | actual set point | -55.0 | 145.0 | -55.0 | °C |
| | | OS1 | low pressure (LP) | 0.0 | 999.0 | 0.0 | (gauge) bar |
| | | OS2 | refrigerant saturation temperature corresponding to the low pressure | -55.0 | 145.0 | -55.0 | °C |
| | | OS3 | refrigerant overheating at the evaporator outlet | -999.0 | 999.0 | -999.0 | K |
| | | OS4 | product average temperature | -55.0 | 145.0 | -55.0 | °C |
| | | OSr | ripening status: 0=off / 1=immediate delay / 2=t1 / 3=t2 / 4=t3 / 5=t4 / 6=t5 | 0 | 255 | 0 | / |
| | | OSt | ripening timer (in countdown-mode) | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | OSY | ethylene status: 0=off / 1=immediate delay / 2=waiting for temperature / 3=first on / 4=first over / 5=following on / 6=following pause / 7=ended / 8=forced | 0 | 255 | 0 | / |
| | | OSU | ethylene timer (in countdown-mode) | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | OnY | remaining following-ethylene-cycles-of-injection, including the one eventually running | 0 | 255 | 0 | / |
| | | OSb | ripening air renew status: 0=off / 1=waiting for ethylene / 2=first pause / 3=on / 4=pause / 5=ended / 6=forced | 0 | 255 | 0 | / |
| | | OSv | ripening air renew timer (in countdown-mode) | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | OnA | remaining air-renew-cycles, including the one eventually running | 0 | 255 | 0 | / |
| | | OSA | storage air renew status: 0=off / 1=immediate delay / 2=on / 3=pause / 4=forced | 0 | 255 | 0 | / |
| | | OSX | storage air renew timer (in countdown-mode) | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | OSd | auxiliary master 1 status: 0=off / 1=ok / 2=check / 3=reconnect / 4=none / 5=lost | 0 | 255 | 0 | / |
| | | OSE | auxiliary master 2 status: 0=off / 1=ok / 2=check / 3=reconnect / 4=none / 5=lost | 0 | 255 | 0 | / |
| | | LLA | actual alarm - read only (0 means no alarm) | 0 | 255 | 0 | / |
| | | OSn | evaporator fan stopped by door opening or manual control | oFF | _on | oFF | / |
| | | Odo | door is opening | oFF | _on | oFF | / |
| | | Odc | door is closing | oFF | _on | oFF | / |
| | | OdF | door light is flashing | oFF | _on | oFF | / |
| | | OdL | room lighting | oFF | _on | oFF | / |
| | | Ocu | curtain is unrolling | oFF | _on | oFF | / |
| | | Ocr | curtain is rolling | oFF | _on | oFF | / |
| | | On1 | depressure fan 1 | oFF | _on | oFF | / |
| | | On2 | depressure fan 2 | oFF | _on | oFF | / |
| | | On3 | depressure fan 3 | oFF | _on | oFF | / |
| | I1A | | Analog inputs - auxiliary master 1 - raw data | | | | |
| | | IA1 | analog input 1 | 0 | 65535 | 0 | / |
| | | IA2 | analog input 2 | 0 | 65535 | 0 | / |
| | | IA3 | analog input 3 | 0 | 65535 | 0 | / |
| | | IA4 | analog input 4 | 0 | 65535 | 0 | / |
| | | IA5 | analog input 5 | 0 | 65535 | 0 | / |
| | | IA6 | analog input 6 | 0 | 65535 | 0 | / |
| | | IA7 | analog input 7 | 0 | 65535 | 0 | / |
| | | IA8 | analog input 8 | 0 | 65535 | 0 | / |
| | I1d | | Digital input | | | | |
| | | Id1 | digital input 1 | oFF | _on | oFF | / |
| | | Id2 | digital input 2 | oFF | _on | oFF | / |
| | | Id3 | digital input 3 | oFF | _on | oFF | / |
| | | Id4 | digital input 4 | oFF | _on | oFF | / |
| | | Id5 | digital input 5 | oFF | _on | oFF | / |
| | O1A | | Analog output | | | | |
| | | OA1 | analog output "FAN" | 0 | 255 | 0 | / |
| | | OA2 | analog output "I out" | 0 | 255 | 0 | / |
| | O1d | | Digital output | | | | |
| | | Od1 | digital output 1 | oFF | _on | oFF | / |
| | | Od2 | digital output 2 | oFF | _on | oFF | / |
| | | Od3 | digital output 3 | oFF | _on | oFF | / |
| | | Od4 | digital output 4 | oFF | _on | oFF | / |
| | | Od5 | digital output 5 | oFF | _on | oFF | / |
| | | Od6 | digital output 6 | oFF | _on | oFF | / |
| | I2A | | Analog inputs - auxiliary master 2 - raw data | | | | |
| | | IA1 | analog input 1 | 0 | 65535 | 0 | / |
| | | IA2 | analog input 2 | 0 | 65535 | 0 | / |
| | | IA3 | analog input 3 | 0 | 65535 | 0 | / |
| | | IA4 | analog input 4 | 0 | 65535 | 0 | / |
| | | IA5 | analog input 5 | 0 | 65535 | 0 | / |
| | | IA6 | analog input 6 | 0 | 65535 | 0 | / |
| | | IA7 | analog input 7 | 0 | 65535 | 0 | / |
| | | IA8 | analog input 8 | 0 | 65535 | 0 | / |
| | I2d | | Digital input | | | | |
| | | Id1 | digital input 1 | oFF | _on | oFF | / |
| | | Id2 | digital input 2 | oFF | _on | oFF | / |
| | | Id3 | digital input 3 | oFF | _on | oFF | / |
| | | Id4 | digital input 4 | oFF | _on | oFF | / |
| | | Id5 | digital input 5 | oFF | _on | oFF | / |
| | O2A | | Analog output | | | | |
| | | OA1 | analog output "FAN" | 0 | 255 | 0 | / |
| | | OA2 | analog output "I out" | 0 | 255 | 0 | / |
| | O2d | | Digital output | | | | |
| | | Od1 | digital output 1 | oFF | _on | oFF | / |
| | | Od2 | digital output 2 | oFF | _on | oFF | / |
| | | Od3 | digital output 3 | oFF | _on | oFF | / |
| | | Od4 | digital output 4 | oFF | _on | oFF | / |
| | | Od5 | digital output 5 | oFF | _on | oFF | / |
| | | Od6 | digital output 6 | oFF | _on | oFF | / |
| E__ | | | Functions about slave preferences | | | | |
| | Ed_ | | Functions about network address | | | | |
| | | EdS | slave address for local network communication | 1 | 254 | 1 | / |
| | EY_ | | Functions about display | | | | |
| | | EYY | input to show on display: 0=average temperature / 1=AN1 / 2=AN2 / ... | 0 | 255 | 0 | / |
| | | EYS | value set by shortcut, during ripening: 0=_t0 / 1=_t1 / … / 5=_t5 / 6=current | 0 | 6 | 6 | / |
| | | EYr | enable display rotation: 0=off / 1=all / 2=selected | 0 | 2 | 0 | / |
| | E0_ | | Functions about display rotation, when EYr=1 | | | | |
| | | E0d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E0E | duration of value display during rotation | 0 | 255 | 2 | / |
| | E1_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E1d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E1t | label text during rotation | 000 | yyy | rM= | / |
| | | E1E | duration of value display during rotation | 0 | 255 | 4 | / |
| | E2_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E2d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E2t | label text during rotation | 000 | yyy | X1= | / |
| | | E2E | duration of value display during rotation | 0 | 255 | 4 | / |
| | E3_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E3d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E3t | label text during rotation | 000 | yyy | SU= | / |
| | | E3E | duration of value display during rotation | 0 | 255 | 0 | / |
| | E4_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E4d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E4t | label text during rotation | 000 | yyy | X2= | / |
| | | E4E | duration of value display during rotation | 0 | 255 | 4 | / |
| | E5_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E5d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E5t | label text during rotation | 000 | yyy | rH= | / |
| | | E5E | duration of value display during rotation | 0 | 255 | 4 | / |
| | E6_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E6d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E6t | label text during rotation | 000 | yyy | Et= | / |
| | | E6E | duration of value display during rotation | 0 | 255 | 0 | / |
| | E7_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E7d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E7t | label text during rotation | 000 | yyy | LP= | / |
| | | E7E | duration of value display during rotation | 0 | 255 | 0 | / |
| | E8_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E8d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E8t | label text during rotation | 000 | yyy | X3= | / |
| | | E8E | duration of value display during rotation | 0 | 255 | 0 | / |
| | E9_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | E9d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | E9t | label text during rotation | 000 | yyy | _t= | / |
| | | E9E | duration of value display during rotation | 0 | 255 | 4 | / |
| | F0_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | F0d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | F0t | label text during rotation | 000 | yyy | LP= | / |
| | | F0E | duration of value display during rotation | 0 | 255 | 0 | / |
| | F1_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | F1d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | F1t | label text during rotation | 000 | yyy | Lt= | / |
| | | F1E | duration of value display during rotation | 0 | 255 | 0 | / |
| | F2_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | F2d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | F2t | label text during rotation | 000 | yyy | oh= | / |
| | | F2E | duration of value display during rotation | 0 | 255 | 0 | / |
| | F3_ | | Functions about display rotation, when EYr=2 (repeated for each parameter) | | | | |
| | | F3d | duration of label display during rotation | 0 | 255 | 1 | / |
| | | F3t | label text during rotation | 000 | yyy | Av= | / |
| | | F3E | duration of value display during rotation | 0 | 255 | 4 | / |
| | Eb_ | | Functions about buzzer | | | | |
| | | EbH | enable buzzer | 0 | 1 | 1 | / |
| | Eh_ | | Functions about keyboard | | | | |
| | | Ehc | B6 action on the curtain: 0=unrolls / 1=rolls | 0 | 1 | 0 | / |
| | EF_ | | Functions about slave default | | | | |
| | | EFF | reload slave default parameters from EEPROM, at next restart | 0 | 1 | 0 | / |