Rem. |
Parameter |
Description |
Minimum |
Maximum |
Default |
Unit |
| S__ | | | Functions about storage | | | | |
| | St_ | | Functions about storage temperature | | | | |
| | | _t0 | storage room temperature | -55.0 | 145.0 | 2.0 | °C |
| | | _td | differential | 0.0 | 50.0 | 0.2 | K |
| | Fd_ | | Functions about defrost duration and timing | | | | |
| | | Fd0 | immediate delay before next defrost | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | Fdd | on-time duration of the defrost | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | Fdg | dripping time after defrost | 0 | 194 4:20:15 | 2:00 | dd hh:mm:ss |
| | | FdE | evaporator fan activation delay after the defrost | 0 | 194 4:20:15 | 7:00 | dd hh:mm:ss |
1 | | | FdP | overall period of the defrost | 0 | 194 4:20:15 | 4:00:00 | dd hh:mm:ss |
| | FF_ | | Functions about forced defrost | | | | |
| | | FFh | enable forced defrost by keyboard short cut | oFF | _on | _on | / |
| | | FFd | forced defrost duration | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
2 | | | FFo | start immediate forced defrost | oFF | _on | oFF | / |
| | FP_ | | Functions about defrost preference | | | | |
| | | FPt | defrost type: 0=none / 1=pause / 2=air / 3=electric / 4=hot gas / 5=heat pump / 6=heat pump by hp | 0 | 4 | 2 | / |
| | Ft_ | | Functions about defrost temperature | | | | |
| | | Ftt | defrost stop temperature | -55.0 | 145.0 | 6.0 | °C |
| n__ | | | Functions about fans | | | | |
| | nE_ | | Functions about evaporator fans | | | | |
| | | nEH | force evaporator fans when refrigeration is off | oFF | _on | oFF | / |
| c__ | | | Functions about door and light | | | | |
| | cP_ | | Door switch and evaporator fan | | | | |
| | | cPH | stop evaporator fans when door is open | oFF | _on | _on | / |
| | | cPF | pause defrost timer when air defrost is suspended by evaporator fan stop | oFF | _on | _on | / |
| | | cPd | delay of fan automatic switch on | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | cI_ | | Functions about light | | | | |
| | | cIH | switch on the light when the door is open and off when closed | oFF | _on | _on | / |
3 | | | cIo | switch off the light automatically if it has been switched on from outside | oFF | _on | _on | / |
| | | cId | delay of light automatic switch off | 0 | 194 4:20:15 | 30 | dd hh:mm:ss |
| v__ | | | Functions about electronic expansion valve | | | | |
| | vP_ | | Functions about electronic expansion valve preference | | | | |
4 | | | vPH | enable electronic expansion valve | oFF | _on | _on | / |
| | vt_ | | Functions about electronic expansion valve temperature | | | | |
5 | | | vtt | wanted overheating (similar to Danfoss thermostatic overheating spring regulation) | -999.0 | 999.0 | 8.0 | K |
| | | vtU | maximum pressure allowed in the suction line (similar to Danfoss MOP) | 0.0 | 999.0 | 10.0 | (gauge) bar |
| | vd_ | | Functions about electronic expansion valve timing | | | | |
6 | | | vd1 | on-off duty cycle duration | 0 | 194 4:20:15 | 8 | dd hh:mm:ss |
7 | | | vd2 | on duty cycle duration at refrigeration start (set to 0 for previous stop value) | 0 | 194 4:20:15 | 5 | dd hh:mm:ss |
8 | | | vdd | on duty cycle adaptation speed (low value for slow adaptation and small swinging) | 0 | 255 | 8 | / |
| b__ | | | Functions about probe calibration | | | | |
| | b1_ | | Probe nr. 1 | | | | |
| | | b1C | room temperature | -999.0 | 999.0 | 0.0 | K |
| | | b1A | enable probe | oFF | _on | _on | / |
| | b2_ | | Probe nr. 2 | | | | |
| | | b2C | defrost temperature | -999.0 | 999.0 | 0.0 | K |
| | | b2A | enable probe | oFF | _on | _on | / |
| | b3_ | | Probe nr. 3 | | | | |
| | | b3C | suction temperature | -999.0 | 999.0 | 0.0 | K |
| | | b3A | enable probe | oFF | _on | _on | / |
| L__ | | | Functions about alarm and stand-by | | | | |
| | Lt_ | | Temperature alarm | | | | |
9 | | | LtL | low temperature alarm set point | -55.0 | 145.0 | -2.0 | °C |
10 | | | LtH | high temperature alarm set point | -55.0 | 145.0 | 14.0 | °C |
| | | Ltd | alarm delay | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | LO_ | | Door alarm | | | | |
| | | LOH | enable door alarm | oFF | _on | _on | / |
| | | LOd | door alarm delay | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | LOt | temperature alarm minimum delay after door opening | 0 | 194 4:20:15 | 15:00 | dd hh:mm:ss |
| | Lo_ | | On / stand-by status | | | | |
| | | Loo | actual status: stand-by or on | oFF | _on | oFF | / |
| P__ | | | Functions about master preferences | | | | |
| | Pd_ | | Functions about network address | | | | |
| | | PdM | master address for global network communication | 0 | 254 | 1 | / |
| | | PdS | number of slaves connected to this master | 1 | 2 | 2 | / |
| I__ | | | Functions about input-output and machine state (read only) | | | | |
| | IA_ | | Analog inputs | | | | |
| | | IA1 | room temperature | -55.0 | 145.0 | -55.0 | °C |
| | | IA2 | defrost temperature | -55.0 | 145.0 | -55.0 | °C |
| | | IA3 | suction temperature | -55.0 | 145.0 | -55.0 | °C |
| | Id_ | | Digital input | | | | |
| | | Id4 | digital input 4 (door closure / remote defrost) - read by IA4 | oFF | _on | oFF | / |
| | OS_ | | Machine status | | | | |
| | | OLP | low pressure (LP) | 0.0 | 999.0 | 0.0 | (gauge) bar |
| | | OSn | evaporator fan stopped by door opening or manual control | oFF | _on | oFF | / |
| | | LLA | actual alarm - read only (0 means no alarm) | 0 | 255 | 0 | / |
| | Od_ | | Digital output | | | | |
11 | | | Od1 | solenoid | oFF | _on | oFF | / |
11 | | | Od3 | light | oFF | _on | oFF | / |
11 | | | Od5 | evaporator | oFF | _on | oFF | / |
11 | | | Od6 | defrost | oFF | _on | oFF | / |
| S__ | | | Functions about storage | | | | |
| | St_ | | Functions about storage temperature | | | | |
| | | _t0 | storage room temperature | -55.0 | 145.0 | 2.0 | °C |
| | | _td | differential | 0.0 | 50.0 | 0.2 | K |
| | Fd_ | | Functions about defrost duration and timing | | | | |
| | | Fd0 | immediate delay before next defrost | 0 | 194 4:20:15 | 0 | dd hh:mm:ss |
| | | Fdd | on-time duration of the defrost | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | Fdg | dripping time after defrost | 0 | 194 4:20:15 | 2:00 | dd hh:mm:ss |
| | | FdE | evaporator fan activation delay after the defrost | 0 | 194 4:20:15 | 7:00 | dd hh:mm:ss |
1 | | | FdP | overall period of the defrost | 0 | 194 4:20:15 | 4:00:00 | dd hh:mm:ss |
| | FF_ | | Functions about forced defrost | | | | |
| | | FFh | enable forced defrost by keyboard short cut | oFF | _on | _on | / |
| | | FFd | forced defrost duration | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
2 | | | FFo | start immediate forced defrost | oFF | _on | oFF | / |
| | FP_ | | Functions about defrost preference | | | | |
| | | FPt | defrost type: 0=none / 1=pause / 2=air / 3=electric / 4=hot gas / 5=heat pump / 6=heat pump by hp | 0 | 4 | 2 | / |
| | Ft_ | | Functions about defrost temperature | | | | |
| | | Ftt | defrost stop temperature | -55.0 | 145.0 | 6.0 | °C |
| n__ | | | Functions about fans | | | | |
| | nE_ | | Functions about evaporator fans | | | | |
| | | nEH | force evaporator fans when refrigeration is off | oFF | _on | oFF | / |
| c__ | | | Functions about door and light | | | | |
| | cP_ | | Door switch and evaporator fan | | | | |
| | | cPH | stop evaporator fans when door is open | oFF | _on | _on | / |
| | | cPF | pause defrost timer when air defrost is suspended by evaporator fan stop | oFF | _on | _on | / |
| | | cPd | delay of fan automatic switch on | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | cI_ | | Functions about light | | | | |
| | | cIH | switch on the light when the door is open and off when closed | oFF | _on | _on | / |
3 | | | cIo | switch off the light automatically if it has been switched on from outside | oFF | _on | _on | / |
| | | cId | delay of light automatic switch off | 0 | 194 4:20:15 | 30 | dd hh:mm:ss |
| v__ | | | Functions about electronic expansion valve | | | | |
| | vP_ | | Functions about electronic expansion valve preference | | | | |
4 | | | vPH | enable electronic expansion valve | oFF | _on | _on | / |
| | vt_ | | Functions about electronic expansion valve temperature | | | | |
5 | | | vtt | wanted overheating (similar to Danfoss thermostatic overheating spring regulation) | -999.0 | 999.0 | 8.0 | K |
| | | vtU | maximum pressure allowed in the suction line (similar to Danfoss MOP) | 0.0 | 999.0 | 10.0 | (gauge) bar |
| | vd_ | | Functions about electronic expansion valve timing | | | | |
6 | | | vd1 | on-off duty cycle duration | 0 | 194 4:20:15 | 8 | dd hh:mm:ss |
7 | | | vd2 | on duty cycle duration at refrigeration start (set to 0 for previous stop value) | 0 | 194 4:20:15 | 5 | dd hh:mm:ss |
8 | | | vdd | on duty cycle adaptation speed (low value for slow adaptation and small swinging) | 0 | 255 | 8 | / |
| b__ | | | Functions about probe calibration | | | | |
| | b1_ | | Probe nr. 1 | | | | |
| | | b1C | room temperature | -999.0 | 999.0 | 0.0 | K |
| | | b1A | enable probe | oFF | _on | _on | / |
| | b2_ | | Probe nr. 2 | | | | |
| | | b2C | defrost temperature | -999.0 | 999.0 | 0.0 | K |
| | | b2A | enable probe | oFF | _on | _on | / |
| | b3_ | | Probe nr. 3 | | | | |
| | | b3C | suction temperature | -999.0 | 999.0 | 0.0 | K |
| | | b3A | enable probe | oFF | _on | _on | / |
| L__ | | | Functions about alarm and stand-by | | | | |
| | Lt_ | | Temperature alarm | | | | |
9 | | | LtL | low temperature alarm set point | -55.0 | 145.0 | -2.0 | °C |
10 | | | LtH | high temperature alarm set point | -55.0 | 145.0 | 14.0 | °C |
| | | Ltd | alarm delay | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | LO_ | | Door alarm | | | | |
| | | LOH | enable door alarm | oFF | _on | _on | / |
| | | LOd | door alarm delay | 0 | 194 4:20:15 | 30:00 | dd hh:mm:ss |
| | | LOt | temperature alarm minimum delay after door opening | 0 | 194 4:20:15 | 15:00 | dd hh:mm:ss |
| | Lo_ | | On / stand-by status | | | | |
| | | Loo | actual status: stand-by or on | oFF | _on | oFF | / |
| I__ | | | Functions about input-output and machine state (read only) | | | | |
| | IA_ | | Analog inputs | | | | |
| | | IA1 | room temperature | -55.0 | 145.0 | -55.0 | °C |
| | | IA2 | defrost temperature | -55.0 | 145.0 | -55.0 | °C |
| | | IA3 | suction temperature | -55.0 | 145.0 | -55.0 | °C |
| | Id_ | | Digital input | | | | |
| | | Id4 | digital input 4 (door closure / remote defrost) - read by IA4 | oFF | _on | oFF | / |
| | OS_ | | Machine status | | | | |
| | | OLP | low pressure (LP) | 0.0 | 999.0 | 0.0 | (gauge) bar |
| | | OSn | evaporator fan stopped by door opening or manual control | oFF | _on | oFF | / |
| | | LLA | actual alarm - read only (0 means no alarm) | 0 | 255 | 0 | / |
| | Od_ | | Digital output | | | | |
11 | | | Od1 | solenoid | oFF | _on | oFF | / |
11 | | | Od3 | light | oFF | _on | oFF | / |
11 | | | Od5 | evaporator | oFF | _on | oFF | / |
11 | | | Od6 | defrost | oFF | _on | oFF | / |