User manual - H424V3

Parameter list

Rem. Parameter Description Minimum Maximum Default Unit
S__Functions about storage
St_Functions about storage temperature
_t0storage room temperature-55.0145.02.0°C
_tddifferential0.050.00.2K
Fd_Functions about defrost duration and timing
Fd0immediate delay before next defrost0194 4:20:150dd hh:mm:ss
Fddon-time duration of the defrost0194 4:20:1530:00dd hh:mm:ss
Fdgdripping time after defrost0194 4:20:152:00dd hh:mm:ss
FdEevaporator fan activation delay after the defrost0194 4:20:157:00dd hh:mm:ss
1FdPoverall period of the defrost0194 4:20:154:00:00dd hh:mm:ss
FdYtemperature display timeout after end of defrost - resets IA1=OS4=OS50194 4:20:1520:00dd hh:mm:ss
FF_Functions about forced defrost
FFhenable forced defrost by keyboard short cutoFF_on_on/
FFdforced defrost duration0194 4:20:1530:00dd hh:mm:ss
2FFostart immediate forced defrostoFF_onoFF/
FP_Functions about defrost preference
FPtdefrost type: 0=none / 1=pause / 2=air / 3=electric / 4=hot gas / 5=heat pump / 6=heat pump by hp042/
3FPcuse door closure input as start command for remote defrostoFF_onoFF/
FPMthis side is defrost master (the instrument is divided in two sides)oFF_onoFF/
FPSthis side is defrost slaveoFF_onoFF/
FPXthis side is defrost slave from aux master (0 means from main master - 255 whatever)02550/
FPYthis side is defrost slave from side nr. (255 means whatever)12551/
Ft_Functions about defrost temperature
Fttdefrost stop temperature-55.0145.06.0°C
n__Functions about fans
nE_Functions about evaporator fans
nEHforce evaporator fans when refrigeration is offoFF_onoFF/
nEFenable evaporator fans during defrostoFF_onoFF/
nEgenable evaporator fans during drippingoFF_onoFF/
c__Functions about door and light
cP_Door switch and evaporator fan
cPHstop evaporator fans when door is openoFF_on_on/
cPFpause defrost timer when air defrost is suspended by evaporator fan stopoFF_on_on/
cPddelay of fan automatic switch on0194 4:20:1530:00dd hh:mm:ss
cI_Functions about light
cIHswitch on the light when the door is open and off when closedoFF_on_on/
4cIoswitch off the light automatically if it has been switched on from outsideoFF_on_on/
cIddelay of light automatic switch off0194 4:20:1530dd hh:mm:ss
v__Functions about electronic expansion valve
vP_Functions about electronic expansion valve preference
5vPHenable electronic expansion valveoFF_on_on/
vPPrefrigerant gas type: 0=R134A / 1=R404A / 2=R507A / 3=R22 / 4=R407C / 5=R407F / 6=R407A / 7=R410A / 8=R290 / 9=R1270 / 10=R744 / 11=R717 / 12=R1234y / 13=R1234z / 14=R449A / 15=R448A / 16=R452A / 17=R450A / 18=R513A / 19=R407H / 20=R23 / 21=R455A040/
6vPdnetwork originating address of the pressure broadcast02550/
vt_Functions about electronic expansion valve temperature
7vttwanted overheating (similar to Danfoss thermostatic overheating spring regulation)-999.0999.08.0K
8vtHmaximum overheating-999.0999.099.0K
9vtLminimum overheating-999.0999.06.0K
vtUmaximum pressure allowed in the suction line (similar to Danfoss MOP)0.0999.010.0(gauge) bar
vd_Functions about electronic expansion valve timing
10vd1on-off duty cycle duration0194 4:20:158dd hh:mm:ss
11vd2on duty cycle duration at refrigeration start (set to 0 for previous stop value)0194 4:20:155dd hh:mm:ss
12vddon duty cycle adaptation speed (low value for slow adaptation and small swinging)02558/
b__Functions about probe calibration
b1_Probe nr. 1
b1Croom temperature-999.0999.00.0K
b1Aenable probeoFF_on_on/
b2_Probe nr. 2
b2Cdefrost temperature-999.0999.00.0K
b2Aenable probeoFF_on_on/
b3_Probe nr. 3
b3Csuction temperature-999.0999.00.0K
b3Aenable probeoFF_on_on/
b4_Probe nr. 4
b4Cunused temperature - eventually used by Id4-999.0999.00.0K
b4Aenable probeoFF_on_on/
L__Functions about alarm and stand-by
Lt_Temperature alarm
13LtLlow temperature alarm set point-55.0145.0-2.0°C
14LtHhigh temperature alarm set point-55.0145.014.0°C
Ltdalarm delay0194 4:20:1530:00dd hh:mm:ss
LO_Door alarm
LOHenable door alarmoFF_on_on/
LOddoor alarm delay0194 4:20:1530:00dd hh:mm:ss
LOttemperature alarm minimum delay after door opening0194 4:20:1515:00dd hh:mm:ss
Lo_On / stand-by status
Looactual status: stand-by or onoFF_onoFF/
P__Functions about master preferences
Pd_Functions about network address
PdMmaster address for global network communication02541/
PdSnumber of slaves connected to this master122/
PdXnumber of aux masters connected to this master - 0 means no aux connected0310/
PdYthis master is the auxiliary nr. - 0 means it is not aux0310/
I__Functions about input-output and machine state (read only)
IA_Analog inputs
IA1room temperature-55.0145.0-55.0°C
IA2defrost temperature-55.0145.0-55.0°C
IA3suction temperature-55.0145.0-55.0°C
IA4unused temperature - eventually used by Id4-55.0145.0-55.0°C
Id_Digital input
Id2evaporator hardware safetyoFF_onoFF/
Id3defrost hardware safetyoFF_onoFF/
Id4digital input 4 (door closure / remote defrost) - read by IA4oFF_onoFF/
Id5phase software safetyoFF_onoFF/
OS_Machine status
OS1low pressure (LP)0.0999.00.0(gauge) bar
OS2refrigerant saturation temperature corresponding to the low pressure-55.0145.0-55.0°C
OS3refrigerant overheating at the evaporator outlet-999.0999.0-999.0K
OS4temperature before defrost - reads IA1 at range reentering after defrost-55.0145.0-55.0°C
OS5set point temperature during defrost - reads IA1 at range reentering after defrost-55.0145.0-55.0°C
OSnevaporator fan stopped by door opening or manual controloFF_onoFF/
OSSdefrost status: 1=normal / 2=defr / 3=drip / 4=fan delay / 5=forced / 6=wait060/
OSFdefrost timer (in countdown-mode)0194 4:20:150dd hh:mm:ss
OSbspecial defrost display in progress - affects OS4 and OS5 (see FdY)oFF_onoFF/
OSYtimer of the temperature display timeout, after the end of defrost (see FdY)0194 4:20:150dd hh:mm:ss
OSXcommunication alarm: 0=normal / 87=out of range / 88=no link / 89=lost link02550/
LLAactual alarm - read only (0 means no alarm)02550/
Od_Digital output
15Od1solenoidoFF_onoFF/
15Od3lightoFF_onoFF/
15Od5evaporatoroFF_onoFF/
15Od6defrostoFF_onoFF/
E__Functions about slave preferences
Ed_Functions about network address
EdSslave address for local network communication12541/
EdXauxiliary master served by this slave - 0 means it is not aux02550/
EY_Functions about display
EYYinput to show on display: 1=IA1 / 2=IA2 ... / 5=OS1 / 6=OS2 ...191/
EYrenable display rotation: 0=off / 1=all / 2=selected020/
EYFdisplay special text during defrost010/
EYtlabel of special text during defrost000yyydEF/
E0_Functions about display rotation, when EYr=1
E0dduration of label display during rotation02551/
E0Eduration of value display during rotation02552/
E1_Functions about display rotation, when EYr=2 (repeated for each parameter)
E1dduration of label display during rotation02550/
E1tlabel text during rotation000yyyrM=/
E1Eduration of value display during rotation02556/
E2_Functions about display rotation, when EYr=2 (repeated for each parameter)
E2dduration of label display during rotation02551/
E2tlabel text during rotation000yyydE=/
E2Eduration of value display during rotation02550/
E3_Functions about display rotation, when EYr=2 (repeated for each parameter)
E3dduration of label display during rotation02551/
E3tlabel text during rotation000yyySU=/
E3Eduration of value display during rotation02550/
E4_Functions about display rotation, when EYr=2 (repeated for each parameter)
E4dduration of label display during rotation02551/
E4tlabel text during rotation000yyydo=/
E4Eduration of value display during rotation02550/
E5_Functions about display rotation, when EYr=2 (repeated for each parameter)
E5dduration of label display during rotation02551/
E5tlabel text during rotation000yyyLP=/
E5Eduration of value display during rotation02554/
E6_Functions about display rotation, when EYr=2 (repeated for each parameter)
E6dduration of label display during rotation02551/
E6tlabel text during rotation000yyyLt=/
E6Eduration of value display during rotation02550/
E7_Functions about display rotation, when EYr=2 (repeated for each parameter)
E7dduration of label display during rotation02551/
E7tlabel text during rotation000yyyoh=/
E7Eduration of value display during rotation02550/
E8_Functions about display rotation, when EYr=2 (repeated for each parameter)
E8dduration of label display during rotation02551/
E8tlabel text during rotation000yyybF=/
E8Eduration of value display during rotation02550/
E9_Functions about display rotation, when EYr=2 (repeated for each parameter)
E9dduration of label display during rotation02551/
E9tlabel text during rotation000yyySF=/
E9Eduration of value display during rotation02550/
Eb_Functions about buzzer
EbHenable buzzer011/
S__Functions about storage
St_Functions about storage temperature
_t0storage room temperature-55.0145.02.0°C
_tddifferential0.050.00.2K
Fd_Functions about defrost duration and timing
Fd0immediate delay before next defrost0194 4:20:150dd hh:mm:ss
Fddon-time duration of the defrost0194 4:20:1530:00dd hh:mm:ss
Fdgdripping time after defrost0194 4:20:152:00dd hh:mm:ss
FdEevaporator fan activation delay after the defrost0194 4:20:157:00dd hh:mm:ss
1FdPoverall period of the defrost0194 4:20:154:00:00dd hh:mm:ss
FdYtemperature display timeout after end of defrost - resets IA1=OS4=OS50194 4:20:1520:00dd hh:mm:ss
FF_Functions about forced defrost
FFhenable forced defrost by keyboard short cutoFF_on_on/
FFdforced defrost duration0194 4:20:1530:00dd hh:mm:ss
2FFostart immediate forced defrostoFF_onoFF/
FP_Functions about defrost preference
FPtdefrost type: 0=none / 1=pause / 2=air / 3=electric / 4=hot gas / 5=heat pump / 6=heat pump by hp042/
3FPcuse door closure input as start command for remote defrostoFF_onoFF/
FPMthis side is defrost master (the instrument is divided in two sides)oFF_onoFF/
FPSthis side is defrost slaveoFF_onoFF/
FPXthis side is defrost slave from aux master (0 means from main master - 255 whatever)02550/
FPYthis side is defrost slave from side nr. (255 means whatever)12551/
Ft_Functions about defrost temperature
Fttdefrost stop temperature-55.0145.06.0°C
n__Functions about fans
nE_Functions about evaporator fans
nEHforce evaporator fans when refrigeration is offoFF_onoFF/
nEFenable evaporator fans during defrostoFF_onoFF/
nEgenable evaporator fans during drippingoFF_onoFF/
c__Functions about door and light
cP_Door switch and evaporator fan
cPHstop evaporator fans when door is openoFF_on_on/
cPFpause defrost timer when air defrost is suspended by evaporator fan stopoFF_on_on/
cPddelay of fan automatic switch on0194 4:20:1530:00dd hh:mm:ss
cI_Functions about light
cIHswitch on the light when the door is open and off when closedoFF_on_on/
4cIoswitch off the light automatically if it has been switched on from outsideoFF_on_on/
cIddelay of light automatic switch off0194 4:20:1530dd hh:mm:ss
v__Functions about electronic expansion valve
vP_Functions about electronic expansion valve preference
5vPHenable electronic expansion valveoFF_on_on/
vPPrefrigerant gas type: 0=R134A / 1=R404A / 2=R507A / 3=R22 / 4=R407C / 5=R407F / 6=R407A / 7=R410A / 8=R290 / 9=R1270 / 10=R744 / 11=R717 / 12=R1234y / 13=R1234z / 14=R449A / 15=R448A / 16=R452A / 17=R450A / 18=R513A / 19=R407H / 20=R23 / 21=R455A040/
6vPdnetwork originating address of the pressure broadcast02550/
vt_Functions about electronic expansion valve temperature
7vttwanted overheating (similar to Danfoss thermostatic overheating spring regulation)-999.0999.08.0K
8vtHmaximum overheating-999.0999.099.0K
9vtLminimum overheating-999.0999.06.0K
vtUmaximum pressure allowed in the suction line (similar to Danfoss MOP)0.0999.010.0(gauge) bar
vd_Functions about electronic expansion valve timing
10vd1on-off duty cycle duration0194 4:20:158dd hh:mm:ss
11vd2on duty cycle duration at refrigeration start (set to 0 for previous stop value)0194 4:20:155dd hh:mm:ss
12vddon duty cycle adaptation speed (low value for slow adaptation and small swinging)02558/
b__Functions about probe calibration
b1_Probe nr. 1
b1Croom temperature-999.0999.00.0K
b1Aenable probeoFF_on_on/
b2_Probe nr. 2
b2Cdefrost temperature-999.0999.00.0K
b2Aenable probeoFF_on_on/
b3_Probe nr. 3
b3Csuction temperature-999.0999.00.0K
b3Aenable probeoFF_on_on/
b4_Probe nr. 4
b4Cunused temperature - eventually used by Id4-999.0999.00.0K
b4Aenable probeoFF_on_on/
L__Functions about alarm and stand-by
Lt_Temperature alarm
13LtLlow temperature alarm set point-55.0145.0-2.0°C
14LtHhigh temperature alarm set point-55.0145.014.0°C
Ltdalarm delay0194 4:20:1530:00dd hh:mm:ss
LO_Door alarm
LOHenable door alarmoFF_on_on/
LOddoor alarm delay0194 4:20:1530:00dd hh:mm:ss
LOttemperature alarm minimum delay after door opening0194 4:20:1515:00dd hh:mm:ss
Lo_On / stand-by status
Looactual status: stand-by or onoFF_onoFF/
I__Functions about input-output and machine state (read only)
IA_Analog inputs
IA1room temperature-55.0145.0-55.0°C
IA2defrost temperature-55.0145.0-55.0°C
IA3suction temperature-55.0145.0-55.0°C
IA4unused temperature - eventually used by Id4-55.0145.0-55.0°C
Id_Digital input
Id2evaporator hardware safetyoFF_onoFF/
Id3defrost hardware safetyoFF_onoFF/
Id4digital input 4 (door closure / remote defrost) - read by IA4oFF_onoFF/
Id5phase software safetyoFF_onoFF/
OS_Machine status
OS1low pressure (LP)0.0999.00.0(gauge) bar
OS2refrigerant saturation temperature corresponding to the low pressure-55.0145.0-55.0°C
OS3refrigerant overheating at the evaporator outlet-999.0999.0-999.0K
OS4temperature before defrost - reads IA1 at range reentering after defrost-55.0145.0-55.0°C
OS5set point temperature during defrost - reads IA1 at range reentering after defrost-55.0145.0-55.0°C
OSnevaporator fan stopped by door opening or manual controloFF_onoFF/
OSSdefrost status: 1=normal / 2=defr / 3=drip / 4=fan delay / 5=forced / 6=wait02550/
OSFdefrost timer (in countdown-mode)0194 4:20:150dd hh:mm:ss
OSbspecial defrost display in progress - affects OS4 and OS5 (see FdY)oFF_onoFF/
OSYtimer of the temperature display timeout, after the end of defrost (see FdY)0194 4:20:150dd hh:mm:ss
OSXcommunication alarm: 0=normal / 87=out of range / 88=no link / 89=lost link02550/
LLAactual alarm - read only (0 means no alarm)02550/
Od_Digital output
15Od1solenoidoFF_onoFF/
15Od3lightoFF_onoFF/
15Od5evaporatoroFF_onoFF/
15Od6defrostoFF_onoFF/

Parameter remarks

Nr. Remark
1The period of each cycle includes on-time + off-time, that is the overall duration of the cycle.
2Following defrost cycles will be aligned to the end of forced one.
3For defrost synchronization of refrigerated expositors.
4No action if the light is switched on from inside the room.
5When off, the refrigeration solenoid is steadily on during cooling.
6The address of the central unit who is broadcasting pressure (usually 1). Use 0 for previous application H425V1 with no origin specification.
7Caution! Low overheating causes liquid return and compressor damage.
8Overheating over the maximum forces valve anticipated opening.
9Overheating under the minimum delays valve opening.
10Caution! Short duty cycle reduces valve life.
11Caution! Low overheating causes liquid return and compressor damage.
12Caution! High adaptation speed causes swing in the suction line and damage to the compressor.
13The low temperature differential is fixed, and alarm status stops at 0.2 °C above the set point.
14The high temperature differential is fixed, and alarm status stops at 0.2 °C under the set point.
15The minus sign on display ("-") signals that output is going to start after a delay.

Alarm list

Display Alarm
A01low temperatureLow temperature limit has been reached.
A02high temperatureHigh temperature limit has been reached.
A03door openTime limit for door opening has been reached.
A04RTC memory lossMemory loss of real time clock [RTC] - timer reset.
A05Side 1 lost defrostSide 1 of the instrument is defrost slave and does not receive any message from the defrost master.
A06Side 2 lost defrostSide 2 of the instrument is defrost slave and does not receive any message from the defrost master.
A07Bad defr. par. side 1Bad defrost parameters for side 1 of the instrument, please ensure: Fdd+Fdg+FdE<FdP, 5 sec<FdP, not concurrent FPS and FPM, nor FPS and FPc, nor PdX and PdY. Put FPt=0 to avoid this check.
A08Bad defr. par. side 2Bad defrost parameters for side 2 of the instrument, please ensure: Fdd+Fdg+FdE<FdP, 5 sec<FdP, not concurrent FPS and FPM, nor FPS and FPc, nor PdX and PdY. Put FPt=0 to avoid this check.

Slave alarm list

Display Alarm
A96slave EEPROMFailed write operation onto the slave EEPROM.
A97out of rangeThe slave address EdS might be out of the master range, the latter going from 1 to PdS.
A98no linkThe slave does not receive any message from the master.
A99lost linkThe slave lost the communication with the master.

Button list

Push button Function
B1esc - silenceExit without saving from any menu - alarm buzzer silence.
B2upUp navigation in the menu.
B3on/stand-by - pauseToggle between on and stand-by - toggle evaporator fan stop.
B4left - lightLeft navigation in the menu - switch the light on and off.
B5down - defrostDown navigation in the menu - force immediate defrost.
B6right - menu - setRight navigation in the menu - display and modify the set point - enter menu.

Led list

Led Function
L1coolingOn during cooling.
L2evaporatorOn during evaporator run - blinking slowly during activation delay.
L3defrostOn during defrost - blinking slowly during dripping.
L4unusedUnused in this application.
L5unusedUnused in this application.
L6unusedUnused in this application.
L7lightOn when lighting is on - blinking slowly during deactivation delay.

Soft command list

Soft command Function

How to ...

How to ... Function
Switch between on and stand-by.Keep pressed B3 button, to activate and deactivate stand-by. In stand-by every output is disabled except light, leds from L1 to L6 blink, timers continue to count.
Stop or restart evaporator fans.Press shortly the B3 button. When the evaporator fans are stopped, the display blinks.
Program the menu.Keep pressed B6 to enter the menu. Navigate up and down with B2 and B5. Select the submenu by B6. Change the parameter by B2 and B5, press B6 to confirm, or B4 to go back without saving. The changes will have effect after the exit from programming pressing B4 repeatedly. Press B1 to exit immediately without saving any parameter.
Show or change temperature set.Press shortly B6 - the display shows the current set point - change it by B2 and B5, and confirm it by B6. As alternative, enter the menu program as explained above, modify the parameter _t0, then confirm it.
Force a defrost.Keep pressed B5.

Shortcut list

Buttons to press Shortcut description - keep pressed 5 seconds
B5 Force an immediate defrost.

Led and push button location

Led and push button legend.