User manual - H425V3

Parameter list

Rem. Parameter Description Minimum Maximum Default Unit
M__Functions about compressor
MU_Functions about pressure switches
ML0suction low pressure regulation (similar to Danfoss RT1AL set point minus half of neutral zone)0.099.02.8(gauge) bar
MLbsuction pressure regulation dead band (ML0 +/- MLb are the upper/lower limits)0.099.00.5bar
MLdsuction pressure regulation differential (loading at ML0+MLb+MLd / unl at ML0-MLb-MLd)0.099.00.2bar
1Md0minimum HP-LP-difference to unload last compressor still running0.099.02.0bar
1Md1minimum HP-LP-difference to leave all the compressors off0.099.00.5bar
MH0discharge (HP) pressure limit forcing the timed compressor unload0.099.024.0(gauge) bar
2MLHlow pressure safety restart ( similar to Danfoss KP15 lp set point )0.099.01.2(gauge) bar
MLLlow pressure safety stop ( similar to Danfoss KP15 lp set point - differential )0.099.00.2(gauge) bar
MHHhigh pressure safety stop ( similar to Danfoss KP15 hp set point )0.099.028.0(gauge) bar
MHLhigh pressure safety restart ( similar to Danfoss KP15 hp set point - differential )0.099.024.0(gauge) bar
3MU1minimum oil differential pressure of compressor nr. 10.099.01.0bar
MU2minimum oil differential pressure of compressor nr. 20.099.01.0bar
4MU3minimum oil differential pressure of compressor nr. 30.099.01.0bar
Mutminimum oil receiver temperature before opening the oil solenoid-55.0145.025.0°C
5MM1usage of mc nr. 1 output: 0=off / 1=on / 2=auto / 3=slave no / 4=slave nc / 5=kriwan052/
MM2usage of mc nr. 2 output: 0=off / 1=on / 2=auto / 3=slave no / 4=slave nc / 5=kriwan052/
MM3usage of mc nr. 3 output: 0=off / 1=on / 2=auto / 3=slave no / 4=slave nc / 5=kriwan052/
6MMHenable external load override on INP-4oFF_onoFF/
7MMdexternal load override delay0194 4:20:151:00:00dd hh:mm:ss
n__Functions about fans
nc_Functions about condenser fans
ncHenable condenser fans when compressor is off and discharge pressure is over maximumoFF_on_on/
8ncrenable condenser fans speed regulationoFF_on_on/
9ncUfan minimum speed025540/
ncdminimum HP-LP-difference to keep on fans0.099.02.0(gauge) bar
n1Hfan 1 start pressure ( similar to Danfoss KP5 set point ) - active just when ncr is oFF0.099.06.0(gauge) bar
n1Lfan 1 stop pressure ( similar to Danfoss KP5 set point - differential )0.099.02.0(gauge) bar
n2Hfan 2 start pressure0.099.07.0(gauge) bar
n2Lfan 2 stop pressure0.099.05.0(gauge) bar
n3Hfan 3 start pressure0.099.08.0(gauge) bar
n3Lfan 3 stop pressure0.099.06.0(gauge) bar
n4Hfan 4 start pressure0.099.09.0(gauge) bar
n4Lfan 4 stop pressure0.099.07.0(gauge) bar
b__Functions about probe calibration
b1_Probe nr. 1
b1Coil receiver temperature-99.099.00.0K
b1Aenable probeoFF_on_on/
b2_Probe nr. 2
b2Cdischarge temperature-99.099.00.0K
b2Aenable probeoFF_on_on/
b3_Probe nr. 3
b3Csuction temperature-99.099.00.0K
b3Aenable probeoFF_on_on/
b4_Probe nr. 4
b4Cmc1 oil pressure-99.099.00.0bar
b4Aenable probeoFF_on_on/
b5_Probe nr. 5
b5Cmc2 oil pressure-99.099.00.0bar
b5Aenable probeoFF_on_on/
b6_Probe nr. 6
b6Cmc3 oil pressure-99.099.00.0bar
b6Aenable probeoFF_on_on/
b7_Probe nr. 7
b7Chigh pressure (HP)-99.099.00.0bar
b7Aenable probeoFF_on_on/
b8_Probe nr. 8
b8Clow pressure (LP)-99.099.00.0bar
b8Aenable probeoFF_on_on/
L__Functions about alarm and stand-by
LI_Other alarm inputs
L1Henable mc1 alarmoFF_on_on/
L1dmc1 alarm delay0194 4:20:1530:00dd hh:mm:ss
L2Henable mc2 alarmoFF_on_on/
L2dmc2 alarm delay0194 4:20:1530:00dd hh:mm:ss
L3Henable mc3 alarmoFF_on_on/
L3dmc3 alarm delay0194 4:20:1530:00dd hh:mm:ss
L4Henable external override alarmoFF_on_on/
L4doverride alarm delay0194 4:20:151:00:00dd hh:mm:ss
L5Henable digital input 5 alarm (compressor phase monitor / thermal overload relay)oFF_on_on/
L5ddigital input 5 alarm delay0194 4:20:151dd hh:mm:ss
Lo_On / stand-by status
10Looactual status: stand-by or onoFF_onoFF/
d__Functions about delays
dF_Delay from previous stop
dF4mc1 start delay0194 4:20:155:00dd hh:mm:ss
dF5mc2 start delay0194 4:20:1510:00dd hh:mm:ss
dF6mc3 start delay0194 4:20:1515:00dd hh:mm:ss
dS4mc1 stop delay0194 4:20:1545dd hh:mm:ss
dS5mc2 stop delay0194 4:20:1530dd hh:mm:ss
dS6mc3 stop delay0194 4:20:1515dd hh:mm:ss
F__Functions about cooling capacity boost
FP_Functions about boost preference
FPPboost mode: 0=off / 1=on / 2=auto02552/
FPMboost mode when not enough info is received: 0=off / 1=on02551/
FPddelay before establishing that not enough info is received0194 4:20:155:00dd hh:mm:ss
FM_Functions about pressure switches in boost mode
FM0suction low pressure regulation0.099.01.8(gauge) bar
FMbsuction pressure regulation dead band0.099.00.5bar
FMdsuction pressure regulation differential0.099.00.2bar
FF_Delays in boost mode
FF4mc1 start delay0194 4:20:151:00dd hh:mm:ss
FF5mc2 start delay0194 4:20:155:00dd hh:mm:ss
FF6mc3 start delay0194 4:20:1510:00dd hh:mm:ss
FS4mc1 stop delay0194 4:20:155:00dd hh:mm:ss
FS5mc2 stop delay0194 4:20:151:00dd hh:mm:ss
FS6mc3 stop delay0194 4:20:1530dd hh:mm:ss
H__Functions about hot gas mode
HP_Functions about hot gas preference
HPPhot gas mode: 0=off / 1=on / 2=all / 3=auto02553/
HPMhot gas mode when not enough info is received: 0=off / 1=on / 2=all02551/
HPddelay to enter hot gas mode = on0194 4:20:155:00dd hh:mm:ss
HPEdelay to enter hot gas mode = all0194 4:20:151:00dd hh:mm:ss
H1_Functions about condenser fans when hot gas mode = on
H1Hfan 1 start pressure0.099.012.0(gauge) bar
H1Lfan 1 stop pressure0.099.06.0(gauge) bar
H2Hfan 2 start pressure0.099.013.0(gauge) bar
H2Lfan 2 stop pressure0.099.011.0(gauge) bar
H3Hfan 3 start pressure0.099.014.0(gauge) bar
H3Lfan 3 stop pressure0.099.012.0(gauge) bar
H4Hfan 4 start pressure0.099.015.0(gauge) bar
H4Lfan 4 stop pressure0.099.013.0(gauge) bar
HA_Functions about condenser fans when hot gas mode = all
A1Hfan 1 start pressure0.099.026.0(gauge) bar
A1Lfan 1 stop pressure0.099.020.0(gauge) bar
A2Hfan 2 start pressure0.099.025.0(gauge) bar
A2Lfan 2 stop pressure0.099.023.0(gauge) bar
A3Hfan 3 start pressure0.099.026.0(gauge) bar
A3Lfan 3 stop pressure0.099.024.0(gauge) bar
A4Hfan 4 start pressure0.099.027.0(gauge) bar
A4Lfan 4 stop pressure0.099.025.0(gauge) bar
HS_Delays in hot gas mode
HS0minimum stop delay for the last mc still running0194 4:20:152:00dd hh:mm:ss
P__Functions about master preferences
Pd_Functions about network address
PdMmaster address for global network communication02541/
PdSnumber of slaves connected to this master122/
Pb_Suction pressure broadcast
PbHenable suction pressure periodic broadcast over the PC netoFF_on_on/
Pbddelay between pressure broadcast messages0194 4:20:1530dd hh:mm:ss
Pbbdelay between latest received message and broadcasting start0194 4:20:152:00dd hh:mm:ss
PbOspecify originating address in the pressure messageoFF_on_on/
Pb1broadcast a packet with low pressure and without additional infooFF_onoFF/
Pb2broadcast a packet with low pressure and additional infooFF_on_on/
PPMbecome network master after Pbb delayoFF_onoFF/
P2Hpoll periodically second central unit for pressure broadcastoFF_onoFF/
P2Mmaster address of second central unit02542/
P2ddelay between pressure broadcast messages of second central unit0194 4:20:1530dd hh:mm:ss
P3Hpoll periodically third central unit for pressure broadcastoFF_onoFF/
P3Mmaster address of third central unit02543/
P3ddelay between pressure broadcast messages of third central unit0194 4:20:1530dd hh:mm:ss
PO_Output assignment
11PO3assign out-3 relay to: 0=condenser fan / 1=oil receiver solenoid / 2=alarm / 3=oil heater / 4=subcooler / 5=off / 6=NC oil sol / 7=oil sol plus subcooler on FAN / 8=NC oil sol plus subcooler on FAN / 9=fourth mc / 10=fourth mc plus subcooler on FAN02550/
I__Functions about input-output and machine state (read only)
IA_Analog inputs
IA1oil receiver temperature-55.0145.0-55.0°C
IA2discharge temperature-55.0145.0-55.0°C
IA3suction temperature-55.0145.0-55.0°C
IA4oil pressure of mc10.030.00.0(gauge) bar
IA5oil pressure of mc20.030.00.0(gauge) bar
IA6oil pressure of mc30.030.00.0(gauge) bar
IA7high pressure (HP)0.030.00.0(gauge) bar
IA8low pressure (LP)0.030.00.0(gauge) bar
Id_Digital input
Id1mc1 hardware safetyoFF_onoFF/
Id2mc2 hardware safetyoFF_onoFF/
Id3mc3 hardware safetyoFF_onoFF/
Id4external overrideoFF_onoFF/
Id5phase software safetyoFF_onoFF/
OA_Analog output
OA1condenser02550/
OA2humidity - 4...20 mA02550/
Od_Digital output
12Od1condenser fan 2oFF_onoFF/
Od2condenser fan 3oFF_onoFF/
Od3condenser fan 4oFF_onoFF/
Od4compressor 1oFF_onoFF/
Od5compressor 2oFF_onoFF/
Od6compressor 3oFF_onoFF/
Od7oil receiver solenoid - eventually connected to OUT-3oFF_onoFF/
Od8alarm - eventually connected to OUT-3oFF_onoFF/
Od9mc1 oil heater - eventually connected to OUT-3oFF_onoFF/
Od0digital output 3oFF_onoFF/
OS_Machine status
OL0actual set point0.0999.00.0(gauge) bar
OLbactual dead band-999.0999.0-999.0bar
OLdactual differential-999.0999.0-999.0bar
O1Hfan 1 start pressure0.0999.00.0(gauge) bar
O1Lfan 1 stop pressure0.0999.00.0(gauge) bar
O2Hfan 2 start pressure0.0999.00.0(gauge) bar
O2Lfan 2 stop pressure0.0999.00.0(gauge) bar
O3Hfan 3 start pressure0.0999.00.0(gauge) bar
O3Lfan 3 stop pressure0.0999.00.0(gauge) bar
O4Hfan 4 start pressure0.0999.00.0(gauge) bar
O4Lfan 4 stop pressure0.0999.00.0(gauge) bar
LLAactual alarm - read only (0 means no alarm)02550/
OM0suction low pressure regulation: 0=unload/1=neutral/2=load02550/
OM1number of running compressors02550/
OM2number of available compressors02550/
OMLlow pressure is insufficient to load the first compressoroFF_onoFF/
OMMlow pressure is insufficient and is going to unload the compressorsoFF_onoFF/
OMHhigh pressure is excessive to load further compressorsoFF_onoFF/
OMihigh pressure is excessive and is going to unload the compressorsoFF_onoFF/
1OMFcompressor forcing for extreme winter conditionsoFF_onoFF/
OSFboost mode02550/
OSHhot gas mode02550/
OHdtimer to enter hot gas mode = on (in countdown-mode)0194 4:20:150dd hh:mm:ss
OHEtimer to enter hot gas mode = all (in countdown-mode)0194 4:20:150dd hh:mm:ss
OFMnot enough info is receivedoFF_onoFF/
OFdtimer for not enough info (in countdown-mode)0194 4:20:150dd hh:mm:ss
ObHautonomous pressure broadcast over the PC netoFF_onoFF/
Obbautonomous broadcast timer (in countdown-mode)0194 4:20:150dd hh:mm:ss
OF4mc1 timer (in countdown-mode)0194 4:20:150dd hh:mm:ss
OF5mc2 timer (in countdown-mode)0194 4:20:150dd hh:mm:ss
OF6mc3 timer (in countdown-mode)0194 4:20:150dd hh:mm:ss
OF0timer of first scheduled compressor (in countdown-mode)0194 4:20:150dd hh:mm:ss
OC0number of active rooms connected to this central unit, and not lost02550/
OC1number of rooms requiring liquid refrigerant02550/
OCHnumber of rooms requiring hot gas02550/
OCtnumber of rooms in turbo mode02550/
OCFnumber of rooms in boost mode02550/
E__Functions about slave preferences
EY_Functions about display
EYYinput to show on display: 1=IA1 / 2=IA2 ...02558/
EYrenable display rotation: 0=off / 1=all / 2=selected020/
E0_Functions about display rotation, when EYr=1
E0dduration of label display during rotation02551/
E0Eduration of value display during rotation02552/
E1_Functions about display rotation, when EYr=2 (repeated for each parameter)
E1dduration of label display during rotation02551/
E1tlabel text during rotation000yyyot=/
E1Eduration of value display during rotation02550/
E2_Functions about display rotation, when EYr=2 (repeated for each parameter)
E2dduration of label display during rotation02551/
E2tlabel text during rotation000yyydi=/
E2Eduration of value display during rotation02550/
E3_Functions about display rotation, when EYr=2 (repeated for each parameter)
E3dduration of label display during rotation02551/
E3tlabel text during rotation000yyySU=/
E3Eduration of value display during rotation02550/
E4_Functions about display rotation, when EYr=2 (repeated for each parameter)
E4dduration of label display during rotation02551/
E4tlabel text during rotation000yyyo1=/
E4Eduration of value display during rotation02550/
E5_Functions about display rotation, when EYr=2 (repeated for each parameter)
E5dduration of label display during rotation02551/
E5tlabel text during rotation000yyyo2=/
E5Eduration of value display during rotation02550/
E6_Functions about display rotation, when EYr=2 (repeated for each parameter)
E6dduration of label display during rotation02551/
E6tlabel text during rotation000yyyo3=/
E6Eduration of value display during rotation02550/
E7_Functions about display rotation, when EYr=2 (repeated for each parameter)
E7dduration of label display during rotation02551/
E7tlabel text during rotation000yyyHP=/
E7Eduration of value display during rotation02554/
E8_Functions about display rotation, when EYr=2 (repeated for each parameter)
E8dduration of label display during rotation02551/
E8tlabel text during rotation000yyyLP=/
E8Eduration of value display during rotation02554/
E9_Functions about display rotation, when EYr=2 (repeated for each parameter)
E9dduration of label display during rotation02551/
E9tlabel text during rotation000yyyL0=/
E9Eduration of value display during rotation02554/
F0_Functions about display rotation, when EYr=2 (repeated for each parameter)
F0dduration of label display during rotation02551/
F0tlabel text during rotation000yyyLb=/
F0Eduration of value display during rotation02550/
F1_Functions about display rotation, when EYr=2 (repeated for each parameter)
F1dduration of label display during rotation02551/
F1tlabel text during rotation000yyyLd=/
F1Eduration of value display during rotation02550/
F2_Functions about display rotation, when EYr=2 (repeated for each parameter)
F2dduration of label display during rotation02551/
F2tlabel text during rotation000yyy1H=/
F2Eduration of value display during rotation02550/
F3_Functions about display rotation, when EYr=2 (repeated for each parameter)
F3dduration of label display during rotation02551/
F3tlabel text during rotation000yyy1L=/
F3Eduration of value display during rotation02550/
F4_Functions about display rotation, when EYr=2 (repeated for each parameter)
F4dduration of label display during rotation02551/
F4tlabel text during rotation000yyy2H=/
F4Eduration of value display during rotation02550/
F5_Functions about display rotation, when EYr=2 (repeated for each parameter)
F5dduration of label display during rotation02551/
F5tlabel text during rotation000yyy2L=/
F5Eduration of value display during rotation02550/
F6_Functions about display rotation, when EYr=2 (repeated for each parameter)
F6dduration of label display during rotation02551/
F6tlabel text during rotation000yyy3H=/
F6Eduration of value display during rotation02550/
F7_Functions about display rotation, when EYr=2 (repeated for each parameter)
F7dduration of label display during rotation02551/
F7tlabel text during rotation000yyy3L=/
F7Eduration of value display during rotation02550/
F8_Functions about display rotation, when EYr=2 (repeated for each parameter)
F8dduration of label display during rotation02551/
F8tlabel text during rotation000yyy4H=/
F8Eduration of value display during rotation02550/
F9_Functions about display rotation, when EYr=2 (repeated for each parameter)
F9dduration of label display during rotation02551/
F9tlabel text during rotation000yyy4L=/
F9Eduration of value display during rotation02550/
Eb_Functions about buzzer
EbHenable buzzer011/
EF_Functions about slave default
EFFreload slave default parameters from EEPROM, at next restart010/

Parameter remarks

Nr. Remark
1To ensure operation in extreme winter conditions, respect to normal ones, compressors may be switched on sooner, and off later.
2When MLH<MLL,there is a delay of 10*(MLL-MLH) seconds on lp switch. Eventual pumpdown restart is over MLH+1 bar.
3Fixed time 120 s and manual reset.
4In H425V3, starting from revision 03, when MU1 and MU3 are 5.0 and b4A and b6A are oFF, use 5NTC controller for compressors without oil pump; connect HP probe on AN-6 and LP on AN-7.
5Caution! Selection by manual override forces compressor to run whatever the high and low pressure; no safety is left except hardware ones. In slave mode the output is used for partialization. In kriwan mode output is off for reset during stand-by.
6Caution! The external override drives the compressors ignoring high and low pressure; no safety is left except hardware ones. It is recommended to close this contact passing through both contacts of a low pressure and high pressure switch like a kp15. The closed contact is interpreted as "load" while the open contact is neutral. The delays dF4 through dF6 are respected.
7After the delay elapsed, the override forces a load. Automatic reset.
8When speed regulation is off the fan is operated on-off.
9Caution! Speed regulation can cause fan fault or electronic board fault. Low and average minimum speed can increase the risk.
10Passing from stand-by to on and at power on, there is a 5 second delay spent in a virtual stand-by.
11In H425V3, starting from revision 02, when PO3 is 4, OUT-3 drives the subcooler liquid solenoid; AN-1 input is the subcooler suction temperature; Mut is the wanted overheating, where 8.0 °C means 8.0 °C; maximum overheating is fixed at 99.0 °C; minimum overheating is fixed at 6.0 °C; n4H is the refrigerant type, where 0.1 bar means R404A; n4L is the cycle period, where 0.8 bar means 8 s; H4H is the initial on-time, where 0.5 bar means 5 s; H4L is the adaptation speed, where 0.8 bar means 8. To turn off the subcooler solenoid, set PO3 to 5. The subcooler is enabled just when all of the available motorcompressors are on. From revision 05, when PO3 is 4, the value of A4H*10, said k, determines when subcooler is on: for k<10 is on when OM2<=OM1+k, all mc are on, except at most k; for 10<=k<20 is on when k-10<=OM1, at least k-10 mc are on; for 20<=k is same of k equal to 0, all mc have to be on. Rest as in revision 02. When PO3 is 6, do as when PO3 is 1, but inverted contact (NC). When PO3 is 7, do as when PO3 is 1, plus subcooler on FAN, with oil temperature on AN-1, suction temperature on AN-3, and A4L as wanted overheating, where 8.0 bar means 8.0 °C; all the rest as above. When PO3 is 8, do as when PO3 is 6, plus subcooler on FAN; all the rest as above.
12The minus sign on display ("-") signals that output is going to start after a delay.

Alarm list

Display Alarm
A01mc 1 alarmPressure switch, thermistors, or any other compressor safety device has disconnected.
A02mc 2 alarmPressure switch, thermistors, or any other compressor safety device has disconnected.
A03mc 3 alarmPressure switch, thermistors, or any other compressor safety device has disconnected.
A04external overrideThe external override contact is driving the controller.
A05mc phaseCompressor overload/thermal relay disconnected, or missing mains phase - manual reset.
A06mc 1 oil pressureOil differential pressure remained under minimum value for 120 seconds - manual reset.
A07mc 2 oil pressureOil differential pressure remained under minimum value for 120 seconds - manual reset.
A08mc 3 oil pressureOil differential pressure remained under minimum value for 120 seconds - manual reset.
A09EEPROM invalidEEPROM invalid.
A10EEPROM read startEEPROM read start failure
A11EEPROM read endEEPROM read end failure
A12EEPROM write startEEPROM write start failure.
A13EEPROM write endEEPROM write end failure.
A14EEPROM write maxEEPROM failure - reached the maximum number of writing attempts.
A15Exc. pr. drop in w. f.Excessive pressure drop through the water filter
A16Ins. w. pr. in ev.Insufficient water pressure drop through the evaporator
A17Ins. w. pr. in any probeInsufficient water pressure in any probe

Slave alarm list

Display Alarm
A96slave EEPROMFailed write operation onto the slave EEPROM.
A97out of rangeThe slave address EdS might be out of the master range, the latter going from 1 to PdS.
A98no linkThe slave does not receive any message from the master.
A99lost linkThe slave lost the communication with the master.

Button list

Push button Function
B1esc - silenceExit without saving from any menu - alarm buzzer silence.
B2upUp navigation in the menu.
B3on / stand-byToggle between on and stand-by.
B4leftLeft navigation in the menu.
B5downDown navigation in the menu.
B6right - menu - setRight navigation in the menu - display and modify the set point - enter menu.

Led list

Led Function
L1compressor 1On during compressor run - blinking slowly during activation and deactivation delay.
L2compressor 2On during compressor run - blinking slowly during activation and deactivation delay.
L3compressor 3On during compressor run - blinking slowly during activation and deactivation delay.
L4condenser fan 1On during condenser run.
L5condenser fan 2On during condenser run.
L6condenser fan 3On during condenser run.
L7condenser fan 4On during condenser run.

Soft command list

Soft command Function
4skip mc delaySkip compressor delay.

How to ...

How to ... Function
Switch between on and stand-by.Keep pressed B3 button, to activate and deactivate stand-by. In stand-by every output is, leds from L1 to L7 blink, timers continue to count.
Program the menu.Keep pressed B6 to enter the menu. Navigate up and down with B2 and B5. Select the submenu by B6. Change the parameter by B2 and B5, press B6 to confirm, or B4 to go back without saving. The changes will have effect after the exit from programming pressing B4 repeatedly. Press B1 to exit immediately without saving any parameter.
Show or change pressure set.Press shortly B6 - the display shows the current set point - change it by B2 and B5, and confirm it by B6. As alternative, enter the menu program as explained above, modify the parameter ML0, then confirm it.

Shortcut list

Buttons to press Shortcut description - keep pressed 5 seconds
/ This instrument has no further shortcuts.

Led and push button location

Led and push button legend.