  • 80% refrigerant reduction;
  • fully digital control;
  • reduced winter consumption.

Usage

The valve is used to compensate for pressure differences between the inside and the outside of cold rooms at temperatures of 0 °C and above.

Compensation is needed because, during normal operation, the pressure inside the room changes with the temperature. For each degree of cooling, the pressure inside the room drops by about 370 Pa, i.e. about 37 kg/m2, while for each degree of warming there is an equal pressure rise. If not compensated, pressure differences can cause panel damage or structural collapse.

While the pressure rise can be reduced by a suitable delay of the evaporator fans after defrosting, the pressure drop cannot be avoided and is more dangerous, because of the extra load it puts on the room ceiling.

The CVP200 valve can be used as an inlet valve, to reduce the pressure drop, and as an outlet valve, to reduce the rise. Please see the application example on this page.

Advantages of CVP200

  • No air passage and no condensation when the valve is closed
  • No metal components, only plastic materials
  • Wear-free gravity closure
  • Easy-to-clean shape

Technical data

  • Operating range: from 0 to +60 °C
  • Opening pressure: 40 Pa (about 4 kg/m2)
  • Valve weight: 1.4 kg